N.Y. Comp. Codes R. & Regs. tit. 6, § 383-7.6
(2) Protective enclosure design. The protective enclosure must be designed to meet the following requirements:
(3) The roof of the protective enclosure and of the disposal unit must be sloped at a gradient of no less than two percent and sufficient to facilitate drainage and prevent ponding of water.
(b) Water infiltration resistance.
The exterior of the disposal units must be protected against water infiltration by at least two barriers to water infiltration. Each barrier must function independently (i.e., the effective performance of each barrier must not require the presence or proper performance of any other barrier). The barriers may be sealant materials, bentonite impregnated panels, polymeric sheet membranes, or other materials or structures.
(c) Cover.
(1) A cover must be installed over the disposal unit during disposal unit closure. The cover must be designed and constructed to:
(4) The requirement for a cover may be satisfied by either a multi-layer cover meeting the requirements of subdivision (d) of this section or an alternative design meeting the requirements of paragraphs (1) through (3) of this subdivision.
(d) Multi-layer earthen cover requirements.
(1) Unless an alternative design is approved by the department, a multi-layer earthen cover must meet the following requirements. The cover must be composed of, at a minimum, the following layers from the disposal unit upward:
(a) Protective enclosure.