N.Y. Comp. Codes R. & Regs. tit. 6, § 373-3.28
(2) Except as provided in paragraph (o)(11) of this section, this section applies to equipment that contains or contacts hazardous wastes with organic concentrations of at least 10 percent by weight that are managed in one of the following:
(5) Equipment that contains or contacts hazardous waste with an organic concentration of at least 10 percent by weight for less than 300 hours per calendar year is excluded from the requirements of subdivisions (c) through (k) of this section if it is identified as required in subparagraph (o)(7)(vi) of this section. Note:
Note:
The requirements of subdivisions (c) through (o) of this section apply to equipment associated with hazardous waste recycling units previously exempt under section 371.1(g)(3)(i) of this Title. Other exemptions under sections 371.1(e) and 373-3.1(a) of this Title are not affected by these requirements.
(6) Purged coatings and solvents from surface coating operations subject to the national emission standards for hazardous air pollutants (NESHAP) for the surface coating of automobiles and light-duty trucks at 40 CFR part 63, subpart III, as incorporated by reference in section 200.10 of this Title, are not subject to the requirements of this section.
(b) Definitions.
As used in this section, all terms shall have the meaning given them in section 373-2.27(b) of this Part, the ECL and Parts 370-374 and 376 of this Title.
(c) Standards: pumps in light liquid service.
(ii) Each pump in light liquid service shall be checked by visual inspection each calendar week for indications of liquids dripping from the pump seal.
(2)
(ii) If there are indications of liquids dripping from the pump seal, a leak is detected.
(3)
(4) Each pump equipped with a dual mechanical seal system that includes a barrier fluid system is exempt from the requirements of paragraph (1) of this subdivision, provided the following requirements are met:
(i) each dual mechanical seal system must be:
(iv) Each pump must be checked by visual inspection, each calendar week, for indications of liquids dripping from the pump seals.
(b) The owner or operator must determine, based on design considerations and operating experience, a criterion that indicates failure of the seal system, the barrier fluid system, or both.
(vi)
(v)
(5) Any pump that is designated, as described in subparagraph (o)(7)(ii) of this section, for no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, is exempt from the requirements of paragraphs (1), (3), and (4) of this subdivision if the pump meets the following requirements:
(6) If any pump is equipped with a closed-vent system capable of capturing and transporting any leakage from the seal or seals to a control device that complies with the requirements of subdivision (k) of this section, it is exempt from the requirements of paragraphs (1) through (5) of this subdivision.
(d) Standards: compressors.
(2) Each compressor seal system as required in paragraph (1) of this subdivision shall be:
(4) Each barrier fluid system as described in paragraphs (1) through (3) of this subdivision shall be equipped with a sensor that will detect failure of the seal system, barrier fluid system, or both.
(5)
(6) If the sensor indicates failure of the seal system, the barrier fluid system, or both based on the criterion determined under subparagraph (5)(ii) of this subdivision, a leak is detected.
(7)
(9) Any compressor that is designated, as described in subparagraph (o)(7)(ii) of this section, for no detectable emission as indicated by an instrument reading of less than 500 ppm above background, is exempt from the requirements of paragraphs (1) through (8) of this subdivision if the compressor:
(ii) is tested for compliance with subparagraph (i) of this paragraph initially upon designation, annually, and at other times as requested by the commissioner.
(e) Standards: pressure relief devices in gas/vapor service.
(1) Except during pressure releases, each pressure relief device in gas/vapor service shall be operated with no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, as measured by the method specified in paragraph (n)(3) of this section.
(2)
(3) Any pressure relief device that is equipped with a closed-vent system capable of capturing and transporting leakage from the pressure relief device to a control device, as described in subdivision (k) of this section, is exempt from the requirements of paragraphs (1) and (2) of this subdivision.
(f) Standards: sampling connecting systems.
(2) Each closed-purge, closed-loop or closed-vent system as required in paragraph (1) of this subdivision shall:
(1)
(g) Standards: open-ended valves or lines.
(3) When a double block and bleed system is being used, the bleed valve or line may remain open during operations that require venting the line between the block valves but shall comply with paragraph (1) of this subdivision at all other times.
(h) Standards: valves in gas/vapor service or in light liquid service.
(2) If an instrument reading of 10,000 ppm or greater is measured, a leak is detected.
(ii) If a leak is detected, the valve shall be monitored monthly until a leak is not detected for two successive months.
(4)
(3)
(5) First attempts at repair include, but are not limited to, the following best practices where practicable:
(6) Any valve that is designated, as described in subparagraph (o)(7)(ii) of this section, for no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, is exempt from the requirements of paragraph (1) of this subdivision if the valve:
(7) Any valve that is designated, as described in subparagraph (o)(8)(i) of this section, as an unsafe-to-monitor valve is exempt from the requirements of paragraph (1) of this subdivision if:
(8) Any valve that is designated, as described in subparagraph (o)(8)(ii) of this section, as a difficult-to-monitor valve is exempt from the requirements of paragraph (1) of this subdivision if:
(1)
(i) Standards: pumps and valves in heavy liquid service, pressure relief devices in light liquid or heavy liquid service, and flanges and other connectors.
(2) If an instrument reading of 10,000 ppm or greater is measured, a leak is detected.
(3)
(5) Any connector that is inaccessible or is ceramic or ceramic-lined (e.g., porcelain, glass, or glass-lined) is exempt from the monitoring requirements of paragraph (1) of this subdivision and from the recordkeeping requirements of subdivision (o) of this section.
(j) Standards: delay of repair.
(3) Delay of repair for valves will be allowed if:
(4) Delay of repair for pumps will be allowed if:
(5) Delay of repair beyond a hazardous waste management unit shutdown will be allowed for a valve if valve assembly replacement is necessary during the hazardous waste management unit shutdown, valve assembly supplies have been depleted, and valve assembly supplies have been sufficiently stocked before the supplies were depleted. Delay of repair beyond the next hazardous waste management unit shutdown will not be allowed unless the next hazardous waste management unit shutdown occurs sooner than six months after the first hazardous waste management unit shutdown.
(k) Standards: closed-vent systems and control devices.
(1) Owners or operators of closed-vent systems and control devices subject to this section shall comply with the provisions of section 373-3.27(d) of this Subpart.
(ii) Any unit that begins operation after December 21, 1990, and is subject to the requirements of this section when operation begins, must comply with the rules immediately (i.e., must have control devices installed and operating on startup of the affected unit); the 30-month implementation schedule does not apply.
(iii)
(iv) Owners and operators of facilities and units that become newly subject to the requirements of this section after December 8, 1997 due to an action other than those described in subparagraph (iii) of this paragraph must comply with all applicable requirements immediately (i.e., must have control devices installed and operating on the date the facility or unit becomes subject to this section; the 30-month implementation schedule does not apply).
(l) Alternative standards for valves in gas/vapor service or in light liquid service: percentage of valves allowed to leak.
(2)
(2) The following requirements shall be met if an owner or operator elects to comply with the alternative standard of allowing two percent of valves to leak:
(3) Performance tests shall be conducted in the following manner:
(m) Alternative standards for valves in gas/vapor service or in light liquid service: skip period leak detection and repair.
(1) An owner or operator subject to the requirements of subdivision (h) of this section may elect for all valves within a hazardous waste management unit to comply with one of the alternative work practices specified in subparagraphs (2)(ii) and (iii) of this subdivision.
(iv) If the percentage of valves leaking is greater than two percent, the owner or operator shall monitor monthly in compliance with the requirements in subdivision (h) of this section, but may again elect to use this subdivision after meeting the requirements of subparagraph (h)(3)(i) of this section.
(n) Test methods and procedures.
(2)
(2) Leak detection monitoring, as required in subdivisions (c) through (m) of this section, shall comply with the following requirements:
(iv) Calibration gases shall be:
(3) When equipment is tested for compliance with no detectable emissions, as required in paragraphs (c)(5) and (d)(9), subdivision (e), and paragraph (h)(6) of this section, the test shall comply with the following requirements:
(4) In accordance with the waste analysis plan required by paragraph (d)(2) of this section, an owner or operator of a facility must determine, for each piece of equipment, whether the equipment contains or contacts a hazardous waste with organic concentration that equals or exceeds 10 percent by weight using the following:
(o) Recordkeeping requirements.
(2) Owners and operators must record the following information in the facility operating record:
(i) For each piece of equipment to which this section applies:
(3) When each leak is detected as specified in subdivisions (c), (d), (h), and (i) of this section, the following requirements apply:
(4) When each leak is detected as specified in subdivisions (c), (d), (h), and (i) of this section, the following information shall be recorded in an inspection log and shall be kept in the facility operating record:
(7) The following information pertaining to all equipment subject to the requirements in subdivisions (c) through (k) of this section shall be recorded in a log that is kept in the facility operating record:
(i) A list of identification numbers for equipment (except welded fittings) subject to the requirements of this section.
(ii)
(iii) A list of equipment identification numbers for pressure relief devices required to comply with paragraph (e)(1) of this section.
(iv)
(8) The following information pertaining to all valves subject to the requirements of paragraphs (h)(7) and (8) of this section shall be recorded in a log that is kept in the facility operating record:
(9) The following information shall be recorded in the facility operating record for valves complying with subdivision (m) of this section.
(10) The following information shall be recorded in a log that is kept in the facility operating record:
(11) The following information shall be recorded in a log that is kept in the facility operating record for use in determining exemptions as provided in the applicability subdivision of this section and other specific sections:
(1)
(a) Applicability.