N.Y. Comp. Codes R. & Regs. tit. 6, § 225-2.5
Any waste oil that is proposed to be burned must meet the minimum limitations in Table 1 below:
TABLE 1
TABLE 1
| Constituent/Property | Limit |
|---|---|
| Polychlorinated Biphenyls (PCB) | < 2 ppm (1) |
| Total Halogens | <= 1,000 ppm (1) |
| Sulfur | See 6 NYCRR 225-1 (2) |
| Gross Heat Content | >= 125,000 (Btu/gal) |
| Arsenic | < 5 ppm (1) |
| Cadmium | < 2 ppm (1) |
| Chromium | < 10 ppm (1) |
| Lead | < 100 ppm (1) |