Mobile refueling stations.
State of New York
(a) The mobile refueling station must be equipped with hose not exceeding 25 feet in length, fitted with an approved interlock nozzle which matches the fuel tank connection of the refueling service vehicle and does not permit transfer of fuel from the mobile refueling station into any vehicle other than the refueling service vehicle.
(b) On mobile refueling stations a manual and fusible shut-off valve shall be installed in the piping at the point where the dispensing hose is attached to the system of piping after the pump discharge.
(c) Pumping rates for mobile refueling stations shall not exceed five gpm measured at the nozzle.