N.Y. Comp. Codes R. & Regs. tit. 19, § 900-2.6
(b) Wind facilities shall meet the setback requirements in Table 1 or manufacturer setbacks, whichever are more stringent. The setback distances shall be measured as a straight line from the centerline or mid-point of the wind turbine tower to the nearest point on the building foundation, property line or feature, as applicable. Compliance with such setbacks (based on the tallest wind turbine model under consideration) shall be shown in the general site plan drawings (or as stand-alone mapping) as required by subparagraph (f)(1)(ii) of this section.
Table 1: Setback Requirements for Wind Turbine Towers
| Structure Type | Wind Turbine Towers setback* |
|---|---|
| Substation | 1.5 times |
| Any Above-ground Bulk Electric System** | 1.5 times |
| Gas Wells (unless waived by landowner and gas well operator) | 1.1 times |
| Public Roads | 1.1 times |
| Property Lines | 1.1 times |
| Non-participating, non-residential Structures | 1.5 times |
| Non-participating Residences | 2 times |
| *1.0 times Wind Turbine Towers setback is equal to the Total Height of the Wind Facility (at the maximum blade tip height). **Operated at 100 kV or higher, and as defined by North American Electric Reliability Corporation Bulk Electric System Definition Reference Document Version 3, August 2018 (see section 900-15.1[e][1][i] of this Part). |
(d) Solar facilities shall meet the setback requirements set forth in Table 2. Compliance with such setbacks listed in Table 2 shall be shown in the general site plan drawings required by subparagraph (f)(1)(i) of this section. Fencing, collection lines, access roads and landscaping may occur within the setback.
Table 2: Setback Requirements for Solar Facility Components
| Setback Type | Solar Facility Setback |
|---|---|
| Non-participating residential property lines | 100 feet |
| Centerline of Public Roads | 50 feet |
| Non-participating property lines (non-residential) | 50 feet |
| Non-participating occupied residences | 250 feet |
(f) Exhibit 5 shall contain:
(1) Site plans of the proposed facility, including the following:
(i) For solar facilities, general site plan drawings (utilizing GIS mapping) of all facility components at a legible common engineering scale (using a scale ratio in feet of at least 1:200), 2 full-size hard copy sets (22″ x 34″ sheets) shall be provided with the application including the following proposed and existing features:
(ii) For wind facilities, general site plan drawings (utilizing GIS mapping) of all facility components at a reasonable legible engineering scale (using a scale ratio in feet of at least 1:200), 2 full-size hard copy sets (22" x 34" sheets) shall be provided with the application), including the following proposed and existing features:
(2) All drawings listed below are to be drawn to scale, or to an exaggerated scale, as appropriate. All such drawings are to be created using computer graphics or computer-aided design software; hand-drawn sketches and drawings may not be used. The following details and plans shall be provided:
(i) Typical elevation drawings indicating the length, width, height, material of construction, color and finish of all buildings, structures, and fixed equipment to be provided for the following: