N.Y. Comp. Codes R. & Regs. tit. 16, § 400.7
(a) All meters shall be adjusted to register accurately with a tolerance of not more than two percent.
(4) In tests conducted in accordance with paragraph (3) of this subdivision, meters shall be tested at the load points specified below:
(5) In tests employing steam as the testing medium and a condensate weighing scale as the reference standard, meters shall be tested at the load points specified below:
(7) The diameter of each main line metering orifice plate removed from service shall be measured and entered on a record which shall be retained for a period of at least one year.
(c) Steam flow meters—head type.
(1) The test made in accordance with section 400.6(a) of this Part of steam flow meters of the head type shall consist of the following:
(4) The diameter of each metering orifice plate removed from service shall be measured and entered on a record which shall be retained for a period of at least one year.
(d) Steam condensate meters.
(b) Steam flow meters—area and velocity types.