N.Y. Comp. Codes R. & Regs. tit. 16, § 255.481
(a) Each operator must inspect each pipeline or portion of pipeline that is exposed to the atmosphere for evidence of atmospheric corrosion, as follows:
| If the pipeline is located: | Then the frequency of inspection is: |
| Onshore Other than a Service Line | At least once every 3 calendar years, but with intervals not exceeding 39 months |
| Onshore Service Line | At least once every 5 calendar years, but within intervals not exceeding 63 months |
| Offshore | At least once each calendar year, but with intervals not exceeding 15 months |