N.Y. Comp. Codes R. & Regs. tit. 16, § 255.383
(3) Service line serving single-family residence means a gas service line that begins at the fitting that connects the service line to the main and serves only one single-family residence (SFR).
(b) Installation required.
An excess flow valve (EFV) installation must comply with the performance standards in section 255.381 of this Part. After April 14, 2017, each operator must install an EFV on any new or replaced service line serving the following types of services before the line is activated:
(5) A single, small commercial customer served by a single service line with a known customer load not exceeding 1,000 SCFH, at the time of meter installation, based on installed meter capacity.
(c) Exceptions to excess flow valve installation requirement.
An operator need not install an excess flow valve if one or more of the following conditions is present:
(4) an EFV meeting performance standards in section 255.381 of this Part is not commercially available to the operator.
(d) Customer's right to request an EFV.
Existing service line customers who desire an EFV on service lines not exceeding 1,000 SCFH and who do not qualify for one of the exceptions in subdivision (c) of this section may request an EFV to be installed on their service lines. If an eligible service line customer requests an EFV installation, an operator must install the EFV at a mutually agreeable date.
(e) Operator notification of customers concerning EFV installation.
Operators must notify customers of their right to request an EFV in the following manner:
(5) Operators of master-meter systems and liquefied petroleum gas (LPG) operators with fewer than 100 customers may continuously post a general notification in a prominent location frequented by customers.
(f) Operator evidence of customer notification.
An operator must make available to the department a copy of the notice or notices currently in use.
(g) Reporting.
Each operator must report the EFV measures detailed in the annual report required by 49 CFR 191.11.
(a) Definitions.
As used in this section: