N.Y. Comp. Codes R. & Regs. tit. 16, § 255.381
(a) Excess flow valves (EFVs) to be used on service lines that operate continuously throughout the year at a pressure not less than 10 psig (69 kPa) must be manufactured and tested by the manufacturer according to an industry specification, or the manufacturer's written specification, to ensure that each valve will:
(3) at 10 psig (69 kPa) close at, or not more than 50 percent above, the rated closure flow rate specified by the manufacturer and upon closure, reduce the gas flow to the level indicated: