N.Y. Comp. Codes R. & Regs. tit. 16, § 255.327
(a) Except as provided in subdivisions (d), (e) and (f) of this section, each buried transmission line, or distribution main operating at 125 psig (862 kPa) or more in a Class 3 or 4 location, must be installed with a minimum cover as follows:
| Normal | ||
|---|---|---|
| Soil | ||
| Inches | Consolidated | |
| (Millimeters) | Rock | |
| Location | ||
| Class 1 locations | 30 (762) | 18 (457) |
| Class 2, 3, and 4 locations | 36 (914) | 24 (610) |
| Drainage ditches of public | ||
| roads and railroad crossings | 36 (914) | 24 (610) |