N.Y. Comp. Codes R. & Regs. tit. 16, § 255.121
(a) Design formula. Design formulas for plastic pipe are determined in accordance with either of the following formulas:
(1) Except as provided in subdivisions (c) through (f) of this section, the design pressure for plastic pipe may not exceed a gauge pressure of 100 psig (689 kPa) for pipe used in:
(2) Plastic pipe may not be used where operating temperatures of the pipe will be:
(4) All plastic pipe must have a listed HDB in accordance with PPI TR-4/2012 (incorporated by reference, see section 255.7 of this Part).
(c) Polyethylene (PE) pipe requirements.
(1) For PE pipe produced after July 14, 2004, but before January 22, 2019, a design pressure of up to 125 psig may be used, provided:
(2) For PE pipe produced after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:
(iv) The wall thickness for a given outside diameter is not less than that listed in the following table: PE Pipe: Minimum Wall Thickness and SDR Values
PE Pipe: Minimum Wall Thickness and SDR Values
| Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) |
| 1/2″ CTS | 0.090 | 7 |
| 3/4″ CTS | 0.090 | 9.7 |
| 1/2″ IPS | 0.090 | 9.3 |
| 3/4″ IPS | 0.095 | 11 |
| 1″ CTS | 0.119 | 11 |
| 1″ IPS | 0.119 | 11 |
| 1 1/4″ IPS | 0.151 | 11 |
| 1 1/2″ IPS | 0.173 | 11 |
| 2″ | 0.216 | 11 |
| 3″ | 0.259 | 13.5 |
| 4″ | 0.265 | 17 |
| 6″ | 0.315 | 21 |
| 8″ | 0.411 | 21 |
| 10″ | 0.512 | 21 |
| 12″ | 0.607 | 21 |
(d) Polyamide (PA-11) pipe requirements.
(1) For PA-11 pipe produced after January 23, 2009, but before January 22, 2019, a DF of 0.40 may be used in the design formula, provided:
(2) For PA-11 pipe produced on or after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:
(iv) the minimum wall thickness for a given outside diameter is not less than that listed in the following table: PA-11 Pipe: Minimum Wall Thickness and SDR Values
PA-11 Pipe: Minimum Wall Thickness and SDR Values
| Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) |
| 1/2″ CTS | 0.090 | 7 |
| 3/4″ CTS | 0.090 | 9.7 |
| 1/2″ IPS | 0.090 | 9.3 |
| 3/4″ IPS | 0.095 | 11 |
| 1″ CTS | 0.119 | 11 |
| 1″ IPS | 0.119 | 11 |
| 1 1/4″ IPS | 0.151 | 11 |
| 1 1/2″ IPS | 0.173 | 11 |
| 2″ | 0.216 | 11 |
| 3″ | 0.259 | 13.5 |
| 4″ | 0.333 | 13.5 |
| 6″ | 0.491 | 13.5 |
P = 2StDF/(D − t)
P = 2SDF/(SDR − 1)
Where:
P = Design pressure, gauge, psig (kPa).
S = For thermoplastic pipe, the hydrostatic design basis (HDB) is determined in accordance with the listed specification at a temperature equal to 73°F (23°C), 100° F (38°C), 120°F (49°C), or 140°F (60°C). In the absence of an HDB established at the specified temperature, the HDB of a higher temperature may be used in determining a design pressure rating at the specified temperature by arithmetic interpolation using the procedure in Part D.2 of PPI TR-3/2012, (incorporated by reference, see section 255.7 of this Part). For reinforced thermosetting plastic pipe, 11,000 psig (75,842 kPa).
t = Specified wall thickness, inches (mm).
D = Specified outside diameter, inches (mm).
SDR = Standard dimension ratio, the ratio of the average specified outside diameter to the minimum specified wall thickness, corresponding to a value from a common numbering system that was derived from the American National Standards Institute (ANSI) preferred number series 10.
DF = Design Factor, a maximum of 0.32 unless otherwise specified for a particular material in this section.
(b) General requirements for plastic pipe and components.
(e) Polyamide (PA-12) pipe requirements. For PA-12 pipe produced after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:
(4) the minimum wall thickness for a given outside diameter is not less than that listed in the following table: PA-12 Pipe: Minimum Wall Thickness and SDR Values
PA-12 Pipe: Minimum Wall Thickness and SDR Values
| Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) |
| 1/2″ CTS | 0.090 | 7 |
| 3/4″ CTS | 0.090 | 9.7 |
| 1/2″ IPS | 0.090 | 9.3 |
| 3/4″ IPS | 0.095 | 11 |
| 1″ CTS | 0.119 | 11 |
| 1″ IPS | 0.119 | 11 |
| 1 1/4″ IPS | 0.151 | 11 |
| 1 1/2″ IPS | 0.173 | 11 |
| 2″ | 0.216 | 11 |
| 3″ | 0.259 | 13.5 |
| 4″ | 0.333 | 13.5 |
| 6″ | 0.491 | 13.5 |
(f) Reinforced thermosetting plastic pipe requirements.
(2) The wall thickness for reinforced thermosetting plastic pipe may not be less than that listed in the following table:
| Nominal size in inches (millimeters) | Minimum wall thickness in inches (millimeters) |
| 2 (51) | 0.060 (1.52) |
| 3 (76) | 0.060 (1.52) |
| 4 (102) | 0.070 (1.78) |
| 6 (152) | 0.100 (2.54) |