N.Y. Comp. Codes R. & Regs. tit. 12, § 23-4.4
(a) Where any excavation is not protected by sloped sides or banks in compliance with Table I of this Subpart, any person in such excavation shall be protected by sheeting, shoring and bracing in compliance with Tables II, III and IV of this Subpart. Sizes of materials listed in the tables are nominal or trade dimensions.
TABLE II
MAXIMUM HORIZONTAL DISTANCE BETWEEN EDGES OF SHEETING
| Excavation Depth | |||
|---|---|---|---|
| Type of Soil | 5 to 10 ft. | Over 10 to 15 ft. | Over 15 to 20 ft. |
| Stiff cohesive soil | Tight | Tight | Tight |
| Noncohesive soil | 2 feet | Tight | Tight |
| Soft cohesive or wet flowing soil | Tight | Tight | Tight |
(c) Each earth-supported shore, strut or brace shall bear against a footing of sufficient area and stability to prevent any subsidence, yield or shifting of such shore, strut or brace.
TABLE III
MINIMUM SIZES OF STRINGERS AND BRACES
Narrow Trenches—Horizontal Cross-Braces Not Longer Than Four Feet
| Trench Depth | Type of Soil | Vertical Spacing of Stringers | Horizontal Spacing of Cross–Braces | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 4 Feet | 6 Feet | |||||||||
| Stringers | Braces | Stringers | Braces | Stringers | Braces | Stringers | Braces | |||
| 5 to 10 ft. | Stiff cohesive | 4 ft. max. | 4 × 4 | 4 × 4 | 6 × 6 or 4 ×8 | 4 × 4 | 6 × 6 | 4 × 4 | 8 × 8 | 4 × 6 |
| Noncohesive | 4 ft. max. | 6 × 6 or 4 ×8 | 4 × 4 | 6 × 6 | 4 × 4 | 6 × 8 | 4 × 4 | 8 × 10 | 6 × 6 | |
| Soft cohesive and wet flowing | 4 ft. max. | 6 × 6 | 4 × 4 | 6 × 10 | 4 × 6 | 8 × 10 | 6 × 6 | 10 × 12 | 6 × 8 | |
| Over 10 to 20 ft. | Stiff cohesive and noncohesive | 4 ft. max. | 4 × 6 | 4 × 4 | 6 × 6 | 4 × 4 | 8 × 8 or 6 ×10 | 4 × 6 | 10 × 10 | 6 × 6 |
| Soft cohesive and wet flowing | 4 ft. max. | 6 × 8 | 6 × 6 | 8 × 10 | 6 × 8 | 10 × 12 | 8 × 8 | * | * | |
| Over 20 ft. | For any trench over 20 feet in depth the sheeting, shoring and bracing systems shall be designed by a professional engineer licensed to practice in the State of New York. A copy of the plans and specifications for any such bracing system shall be kept at the job site available for examination by the commissioner. |
*
Sizes of timber for such conditions become excessive. A special structure designed by a professional engineer licensed to practice in the State of New York shall be constructed and used for the specific condition involved.
Note: Timber sizes are nominal or trade dimensions.