N.Y. Comp. Codes R. & Regs. tit. 12, § 23-1.14
(3) Temporary combustion devices shall not be placed on any combustible floor, platform or any other combustible surface unless such surface is protected or insulated for a minimum distance of six feet in a horizontal direction from the perimeter of the combustion device on all sides. The minimum overhead or side clearance from the combustion device to any combustible material shall be four feet. Exception:
Exception:
The horizontal insulation protection on a scaffold platform may be limited to the width of the scaffold platform provided there are no combustible objects or materials within six feet horizontally in any direction from the combustion device and that the other pertinent provisions of this section are complied with.
(6) Solid fuel heaters and oil-fired salamanders are prohibited from use in any building or other structure under construction or from use on any scaffold.
(b) Temporary combustion devices using liquefied gas.
(1) General.
(2) Liquefied gas cylinders and containers. Exception: Exception:
(i) Cylinders and containers of liquefied gas used as fuel for the heating of construction shanties, sanitary facilities, field offices or other temporary buildings or structures on construction, demolition or excavation sites shall be located outside such buildings or other structures.
Exception:
Temporary combustion devices specifically designed to be attached to gas cylinders or containers.
(vi) Liquefied gas cylinders or containers, whether full, partially full or empty, shall be securely fastened in place in an upright position and protected from any damage. Such cylinders shall not be supported in the areas of the valves or valve protectors.
Exception:
In operations where such cylinders must be placed in a horizontal position, as in the extraction of liquid.
(3) Central station distribution. Where temporary combustion devices use liquefied gas supplied from a central station, the liquefied gas distribution shall be in accordance with the following:
(4) Use of individual liquefied gas cylinders or containers. Where each temporary combustion device is supplied with liquefied gas from an individual cylinder or container and a central station distribution system is not used, such use shall be in accordance with the following: Exception: Exception:
(ii) Each liquefied gas cylinder or container shall be located a minimum distance of six feet from any temporary combustion device.
Exception:
Any temporary combustion device specifically designed to be attached to a gas cylinder or container.
(iii) Liquefied gas cylinders or containers shall be connected to temporary combustion devices by means of armored flexible hose not more than 10 feet nor less than six feet in length.
Exception:
Any temporary combustion device specifically designed to be attached to a gas cylinder or container.
(a) General requirements.