N.Y. Comp. Codes R. & Regs. tit. 12, § 14-10.13

Setting of safety valves.

Department of Labor

One or more safety valves on every boiler shall be set at or below the maximum allowable working pressure. The remaining valves may be set within a range of three percent above the maximum allowable working pressure, but the range of setting of all of the valves on a boiler shall not exceed 10 percent of the highest pressure to which any valve is set.