N.Y. Comp. Codes R. & Regs. tit. 12, § 14-1.17
Pressure controls.
Department of Labor
- (a) Each automatically fired steam power boiler shall have at least one steam pressure control device that will shut off the fuel supply to each boiler when the steam pressure reaches a preset maximum operating pressure.
- (b) In addition to the pressure control required in subdivision (a) of this section, each automatically fired steam power boiler installed after the effective date of this Subpart shall have a high limit manual reset steam pressure control that will prevent generation of steam pressure in excess of the maximum allowable working pressure.
- (c) The flame safeguard requirements for high pressure boilers should be the same as they are for low pressure boilers (see Code Rule 4, Subparts 4-9, 4-10, 4-11 and 4-12 of this Part).
The exceptions in section 14-1.14(a) of this Subpart also apply to the following requirements: