N.Y. Comp. Codes R. & Regs. tit. 12, § 14-1.12
Blowoff tanks.
Department of Labor
- (a) Boilers operating at pressures in excess of 100 psi and boilers not having a safe place of discharge shall be provided with blowoff tanks. The blowoff tanks shall be constructed in accordance with the provisions of the ASME Code, section VIII, division 1.
- (b) The outlet from the blowoff tank shall be twice the area of the boiler blowoff pipe and made to extend internally within six inches from the bottom of the tank.
- (c) A vent pipe, at least twice the diameter to the inlet, shall lead to the outside atmosphere.
- (d) Vents shall be as direct as possible to the outside atmosphere and discharge at a point not less than seven feet above the adjacent walkway or areas without a valve or other possible obstruction such as a water pocket.
- (e) For convenience in cleaning the tank, a manhole or an access opening shall be provided in the upper head or shell of same.
- (f) All pipe connections between tank and blowoff valves on the boiler shall be made as direct as possible. The piping and fittings shall be in accordance with the ASME Code.