N.Y. Comp. Codes R. & Regs. tit. 10, § 713-3.24
(b) Thermal insulation and acoustical insulation (if applicable) shall be provided on the following fixtures and equipment in the nursing home facility and shall comply with the following:
(c) Steam and hot water systems shall comply with the following:
(d) Heating, cooling and ventilating systems for resident occupied areas of the facility shall comply with the following minimum standards except where other minimum standards are shown on Table 8 of this subdivision:
(2) All air-supply and air-exhaust systems shall be mechanically operated. All fans serving exhaust systems shall be located at the discharge end of the system. The ventilation rates shown in Table 8 of this subdivision shall be considered as minimum acceptable rates and shall not be construed as precluding the use of higher ventilation rates provided such higher rates do not result in undesirable air velocity in resident-use areas. TABLE 8 PRESSURE RELATIONSHIPS AND VENTILATION OF NURSING HOME FACILITIES TABLE 9 FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR CONDITIONING SYSTEMS IN NURSING HOME FACILITIES *
(ii) The ventilation systems shall be designed and balanced to provide the pressure relationship as shown in Table 8 of this section (below).
TABLE 8 PRESSURE RELATIONSHIPS AND VENTILATION OF NURSING HOME FACILITIES
| Area designation | Pressure relationship adjacent areas | Minimum air changes of outdoor air per hour supplied to room | Minimum total air changes per hour supplied to room | All air exhausted directly to outdoors | Recirculated within room units |
|---|---|---|---|---|---|
| Resident Room | E | 2 | 2 | Optional | Optional |
| Resident Area Corridor | E | 2 | 4 | Optional | Optional |
| Examination and Treatment Room | E | 2 | 6 | Optional | Optional |
| Physical Therapy | N | 2 | 6 | Optional | Optional |
| Occupational Therapy | N | 2 | 6 | Optional | Optional |
| Soiled Workroom or Soiled Holding | N | 2 | 10 | Yes | No |
| Clean Workroom or Clean Holding | P | 2 | 4 | Optional | Optional |
| Toilet Room | N | Optional | 10 | Yes | No |
| Bathroom | N | Optional | 10 | Yes | No |
| Janitors' Closets | N | Optional | 10 | Yes | No |
| Sterilizer Equipment Rooms | N | Optional | 10 | Yes | No |
| Linen and Trash Chute Rooms | N | Optional | 10 | Yes | No |
| Food Preparation Center | E | 2 | 10 | Yes | No |
| Warewashing Room | N | Optional | 10 | Yes | No |
| Dietary Day Storage | E | Optional | 2 | Yes | No |
| Laundry, General | E | 2 | 2 | Yes | No |
| Soiled Linen Sorting and Storage | N | Optional | 10 | Yes | No |
| Clean Linen Storage | P | 2 | 2 | Optional | Optional |
| P = Positive N = Negative E = Equal |
(v) All central ventilation or air conditioning systems shall be equipped with filters having efficiencies no less than those specified in Table 9 of this subdivision, below. The filter bed shall be located upstream of the air conditioning equipment, unless a prefilter is employed. In this case, the prefilter shall be upstream of the equipment and the main filter may be located further downstream.
TABLE 9
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR CONDITIONING SYSTEMS IN NURSING HOME FACILITIES
| Area designation | Minimum number of filter beds | Filter efficiency (percent) main filter bed |
|---|---|---|
| Resident Care, Treatment Diagnostic & Related Areas | 1 | 80* |
| Food Preparation Areas and Laundries | 1 | 80 |
| Administrative, Bulk Storage and Soiled Holding Areas | 1 | 25 |
*
May be reduced to 35 percent for all outdoor air systems.
(e) All plumbing systems and other piping systems shall be designed and installed in accordance with the requirements of the local or municipal building code authority having jurisdiction.
(1) Plumbing fixtures shall comply with the following:
(2) Water supply systems shall comply with the following:
(3) Hot water heating systems shall comply with the following:
(ii) Storage tank(s) shall be fabricated of corrosion-resistant metal or lined with non-corrosive material.
| Clinical | USE Dietary | Laundry | |
| Gallons (per hour per resident) | 6 1/2 | 4 | 4 1/2 |
| Liters (per second per resident) | .007 | .004 | .005 |
| Temperature (F) | 110* | 180 | 180 |
*Maximum
(4) Drainage systems shall comply with the following requirements: