N.Y. Comp. Codes R. & Regs. tit. 10, § 713-2.21
(b) Thermal insulation and acoustical insulation (if applicable) shall be provided on the following fixtures and equipment within a nursing home facility and shall comply with the following:
(c) Steam and hot water systems shall comply with the following:
(d) Heating and ventilating systems shall comply with the following:
(2) All air-supply and air-exhaust systems shall be mechanically operated. All fans serving exhaust systems shall be located at the discharge end of the system. The ventilation rates shown in Table 8 of this section shall be considered as minimum acceptable rates and shall not be construed as precluding the use of higher ventilation rates.
(ii) The ventilation systems shall be designed and balanced to provide the pressure relationship as shown in Table 8, below.
TABLE 8
PRESSURE RELATIONSHIPS AND VENTILATION OF CERTAIN AREAS OF
NURSING HOME FACILITIES
| Area Designation | Pressure relationship to adjacent areas | Minimum air changes of outdoor air per hour supplied to room | Minimum total air changes per hour supplied to room | All air exhausted directly to outdoors | Recirculated within room units |
| Patient Room | E | 2 | 2 | Optional | Optional |
| Patient Area Corridor | E | 2 | 4 | Optional | Optional |
| Examination & Treatment Room | E | 2 | 6 | Optional | Optional |
| Physical Therapy | N | 2 | 6 | Optional | Optional |
| Occupational Therapy | N | 2 | 6 | Optional | Optional |
| Soiled workroom or soiled holding | N | 2 | 10 | Yes | No |
| Clean workroom or clean holding | P | 2 | 4 | Optional | Optional |
| Toilet room | N | Optional | 10 | Yes | No |
| Bathroom | N | Optional | 10 | Yes | No |
| Janitor closet | N | Optional | 10 | Yes | No |
| Sterilizer Equipment room | N | Optional | 10 | Yes | No |
| Linen & trash chute room | N | Optional | 10 | Yes | No |
| Food Prep Center | E | 2 | 10 | Yes | No |
| Warewashing Room | N | Optional | 10 | Yes | No |
| Dietary Day Storage | E | Optional | 2 | Yes | No |
| General Laundry | E | 2 | 10 | Yes | No |
| Soiled linen sorting & storage | N | Optional | 10 | Yes | No |
| Clean linen storage | P | 2 | 2 | Optional | Optional |
| P=Positive N=Negative E=Equal |
(v) All central ventilation or air conditioning systems shall be equipped with filters having efficiencies no less than those specified in Table 9, below. The filter bed shall be located upstream of the air conditioning equipment, unless a prefilter is employed. In this case, the prefilter shall be upstream of the equipment and the main filter may be located further downstream.
TABLE 9
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR CONDITIONING
SYSTEMS IN NURSING HOME FACILITIES
| Area designation | Minimum number of filter beds | Filter efficiency (percent) of main filter bed |
| Resident Care, Treatment, Diagnostic and Related Areas | 1 | 80* |
| Food Preparation Areas and Laundries | 1 | 80 |
| Administrative, Bulk Storage and Soiled Holding Areas | 1 | 25 |
| *May be reduced to 35 percent for all outdoor air systems. |
(x) Fire and smoke dampers shall be constructed, located and installed in accordance with the requirements of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, 1999 edition. Access for maintenance shall be provided at all dampers. Further details concerning the material referenced herein are contained in section 711.2(a) of this Title.
(xii) Boiler room shall be provided with sufficient outdoor air to maintain combustion rates of equipment and to limit temperature in working stations to 97°F.
(e) All plumbing and other piping systems shall comply with this subdivision.
(1) Plumbing fixtures shall comply with the following:
(2) Water supply systems shall comply with the following:
(3) Hot water heaters and tanks shall comply with the following:
(ii) Storage tank(s) shall be fabricated of corrosion-resistant metal or lined with non-corrosive material.
| Use | Gallons (per hour per bed) | Liters (per second per bed) | Temperature (oF) |
| Clinical | 6-½ | .007 | 110 |
| Dietary | 4 | .004 | 180 |
| Laundry | 4-½ | .005 | 180 |
(4) Drainage systems shall comply with the following: