N.Y. Comp. Codes R. & Regs. tit. 10, § 712-1.27
(d) Air conditioning systems shall be provided, capable of maintaining temperature and relative humidity at or between the following ranges:
| Temperature (°F) | Relative Humidity (%) | |
| Operating Rooms | 70 - 76 | 50 - 60 |
| Recovery Rooms | 75 | 50 - 60 |
| Intensive Care Rooms | 75 - 80 | 30 - 60 |
| Delivery Rooms | 71 - 75 | 50 |
| Nurseries | 75 - 80 | 30 - 60 |
Filters for the above systems shall be provided with a minimum efficiency of 90 percent.
(p) The hot water heating equipment shall have sufficient capacity to supply water at the temperatures and amounts indicated below. The water temperature is to be taken at hot water point of use or inlet to processing equipment.
| Clinical | Dietary | Laundry | |
| Gallons (per hour per bed) | 6-¼ | 4 | 4-½ |
| Temperature (°F) | 110 | 120* | 160** |
*Wash water and rinse water when used as the sanitizer is to be provided at the temperature required by the equipment manufacturer, and 170°F when manual methods are used.
**Lower temperature is permitted if a controlled program of sanitizing has prior approval of the department.