N.Y. Comp. Codes R. & Regs. tit. 10, § 67-4.3
(b) First-draw samples shall be collected from all outlets, as defined in this Subpart. A first-draw sample volume shall be 250 milliliters (mL), collected from a cold water outlet before any water is used. The water shall be motionless in the pipes for a minimum of 8 hours, but not more than 18 hours, before sample collection. First-draw samples shall be collected pursuant to such other specifications as the department may determine appropriate.
(1) For existing buildings in service as of September 6, 2016, schools shall complete collection of initial first-draw samples according to the following schedule:
(c) Initial first-draw samples.