N.Y. Comp. Codes R. & Regs. tit. 10, § 5-1.81
(1) Initial round of source water monitoring. Systems shall conduct the following monitoring, based on the monitoring schedule prescribed in paragraph (3) of this subdivision, unless they meet the monitoring exemption criteria in paragraph (4) of this subdivision:
(iii) Filtered systems serving fewer than 10,000 people:
(c) shall sample their source water for Cryptosporidium at least twice per month for 12 months, or at least monthly for 24 months, if, based on monitoring conducted under this subparagraph, they meet one of the following criteria:
(4) Monitoring avoidance.
(5) Plants operating only part of the year. Systems with surface water sources or ground water sources directly influenced by surface water and with plants that operate for only part of the year shall conduct source water monitoring in accordance with this section and section 5-1.80 of this Subpart, but with the following modifications:
(6) New sources.
(iii) The system shall begin a second round of source water monitoring no later than six years following initial bin classification or determination of the mean Cryptosporidium level, as applicable.
(b) Sampling schedules.
(2) Systems shall collect samples within two days before or two days after the dates indicated in their sampling schedule, unless one of the following conditions applies:
(3) Systems that fail to meet the criteria of paragraph (2) of this subdivision for any source water sample required under subdivision (a) of this section shall revise their sampling schedules to add dates for collecting all missed samples. Systems shall submit the revised schedule to the State for approval prior to when the system begins collecting the missed samples.
(c) Sampling locations.
(4) Bank filtration.
(5) Multiple sources. Systems with plants that use multiple water sources, including multiple surface water sources and blended surface water and ground water sources, shall collect samples as specified in subparagraph (i) or (ii) of this paragraph. The use of multiple sources during monitoring shall be consistent with routine operational practice.
(ii) If a sampling tap where the sources are combined prior to treatment is not available, systems shall collect samples at each source near the intake on the same day and select one of the following options for sample analysis:
(6) Additional requirements. Systems shall submit a description of their sampling location(s) to the State at the same time as the sampling schedule. This description shall address the position of the sampling location in relation to the system’s water source(s) and treatment processes, including pretreatment, points of chemical treatment, and filter backwash recycle. If the State does not respond to a system regarding sampling location(s), the system shall sample at the reported location(s).
(d) Reporting source water monitoring results.
(2) Systems shall report the following information, as applicable, for the source water monitoring samples required under subdivision (a) of this section:
(i) Systems shall report the following data elements for each Cryptosporidium analysis: PWS ID; facility ID sample collection date sample type (field or matrix spike); sample volume filtered (in liters, to the nearest 0.25 liter); confirmation that 100 percent of filtered volume was examined; and the number of oocysts counted.
(a) Source water monitoring.