- A. Each facility and each floor of a facility must have exits as required/permitted by the National Fire Protection Association 101 (Life Safety Code) or Uniform Building Code.
- B. Each facility must have at least two approved exits, remote from each other.
- C. Each exit must be clearly marked with signs having letters at least six inches high whose principal strokes are at least : of an inch wide. Exit signs must be visible at all times.
- D. Exits, exit paths, or means of egress must not pass through hazardous areas, storerooms, closets, bedrooms, or spaces subject to locking.
- E. Sliding doors are not considered acceptable as required exits.
- F. When illuminated exit signs are present, they are maintained in operable condition.
- G. Exit ways must be kept free from obstructions at all times.
- H. Exit doors must be at least 36” wide.
[7.8.3.114 NMAC – N, 05/15/01]