N.M. Code R. § 7.20.12.70
B. Circuit breakers or fused switches that provide electrical disconnection and overcurrent protection must be:
(1) enclosed or guarded to provide a dead front assembly;
(2) readily accessible for use and maintenance;
(3) set apart from traffic lanes;
(4) located in a dry, ventilated space, free of corrosive fumes or gases;
(5) able to operate properly in all temperature conditions;
(6) located on the same floor and in the same facility area as the circuits they serve;
(7) marked showing the area each circuit breaker or fused switch services.
C. The use of jumpers or devices to bypass circuit breakers or fused switches is prohibited.
[1/1/99; 7.20.12.70 NMAC - Rn, 7 NMAC 20.12.70, 02/28/05]