- A. A cylinder exchange installation registration form and approved plans shall be required prior to installation.
- B. Installation shall meet the requirements of NFPA 58.
- C. Cylinder exchange cabinets shall be approved, and meet the requirements of NFPA 58; excepting cylinder exchange cabinet installations shall comply with Subsection D if installed greater than five feet from a building or approved in writing by the LP gas bureau chief.
D. Protection against vehicle impact shall be crash post or other protection acceptable to the LP gas bureau.
- (1) Crash post shall be installed as required elsewhere in this document.
(2) A minimum six inch high concrete raised sidewalks or six inch high wheel stops can be used.
- (a) The minimum distance from the raised sidewalks or wheel stops to the cabinet shall be 48 inches.
- (b) The wheel stops shall be anchored and secured with at least five-eighths inch by 18 inch steel rods.
- E. Cylinder exchange installations in excess of 720 lb propane stored shall be provided with at least one approved portable fire extinguisher having a minimum capacity of 18 lb dry chemical with B:C rating.
[19.15.40.21 NMAC - N, 2/1/2006; A, 7/1/2018]