N.M. Code R. § 14.9.2.13
See this chapter of the UMC except as provided below. 511.3 Makeup Air. See this section of the UMC except add the following: windows and doors shall not be used for the purpose of providing makeup air. The exhaust and makeup air systems shall be connected by an electrical interlocking switch. A device to sense continued air movement within the makeup air plenum shall be installed initiating a complete system shut-down if air-flow is interrupted.
[14.9.2.13 NMAC - Rp, 14.9.2.13 NMAC, 05/15/2018; A, 3/10/2022]