N.M. Code R. § 14.7.4.18
C. Lintels over openings in stabilized rammed earth walls. Openings less than 2four inches in width shall not require a lintel or semi-circular arched opening. Openings greater than 2four inches in width require lintels as defined in Table 4.
Table 4 Concrete Lintels Over Openings in Rammed Earth Walls (1) Wall width Lintel span Lintel depth Reinforcement (2) Reinforcement Concrete Cover (3) Uniform Load 18” 24” 6” 3- #4 @ 4”o.c. 3” minimum concrete cover on all sides 1000 PLF 36” 6” 3- #4 @ 4”o.c. 48” 6” 3- #4 @ 4”o.c. 60” 6” 3- #4 @ 4”o.c. 72” 8” 3- #5 @ 4”o.c. 84” 8” 3- #5 @ 4”o.c. 96” 8” 3- #5 @ 4”o.c. 20” 24” 6” 3- #4 @ 4”o.c. 4” minimum concrete cover on all sides 1350 PLF 36” 6” 3- #4 @ 4”o.c. 48” 6” 3- #4 @ 4”o.c. 60” 6” 3- #4 @ 4”o.c. 72” 8” 3- #5 @ 4”o.c. 84” 8” 3- #5 @ 4”o.c. 96” 10” 3- #5 @ 4”o.c. 22” 24” 6” 3- #4 @ 5”o.c. 3 1/2” minimum concrete cover on all sides 1700 PLF 36” 6” 3- #4 @ 5”o.c. 48” 6” 3- #4 @ 5”o.c. 60” 6” 3- #4 @ 5”o.c. 72” 8” 3- #5 @ 5”o.c. 84” 10” 3- #5 @ 5”o.c. 96” 10” 3- #5 @ 5”o.c. 24” 24” 6” 3- #4 @ 6”o.c. 3” minimum concrete cover on all sides 2000 PLF 36” 6” 3- #4 @ 6”o.c. 48” 6” 3- #4 @ 6”o.c. 60” 6” 3- #4 @ 6”o.c. 72” 8” 3- #5 @ 6”o.c. 84” 10” 3- #5 @ 6”o.c. 96” 12” 3- #5 @ 6”o.c. 1. 3000 psi minimum concrete at approximately 28 days. 2. Grade 40 steel reinforcement minimum. 3. Steel reinforcement at mid-depth of lintel.
Table 4 Concrete Lintels Over Openings in Rammed Earth Walls (1)
Wall width
Lintel span
Lintel depth
Reinforcement (2)
Reinforcement Concrete Cover (3)
Uniform Load
18”
24”
6”
3- #4 @ 4”o.c.
3” minimum concrete cover on all sides
1000 PLF
36”
6”
3- #4 @ 4”o.c.
48”
6”
3- #4 @ 4”o.c.
60”
6”
3- #4 @ 4”o.c.
72”
8”
3- #5 @ 4”o.c.
84”
8”
3- #5 @ 4”o.c.
96”
8”
3- #5 @ 4”o.c.
20”
24”
6”
3- #4 @ 4”o.c.
4” minimum concrete cover on all sides
1350 PLF
36”
6”
3- #4 @ 4”o.c.
48”
6”
3- #4 @ 4”o.c.
60”
6”
3- #4 @ 4”o.c.
72”
8”
3- #5 @ 4”o.c.
84”
8”
3- #5 @ 4”o.c.
96”
10”
3- #5 @ 4”o.c.
22”
24”
6”
3- #4 @ 5”o.c.
3 1/2” minimum concrete cover on all sides
1700 PLF
36”
6”
3- #4 @ 5”o.c.
48”
6”
3- #4 @ 5”o.c.
60”
6”
3- #4 @ 5”o.c.
72”
8”
3- #5 @ 5”o.c.
84”
10”
3- #5 @ 5”o.c.
96”
10”
3- #5 @ 5”o.c.
24”
24”
6”
3- #4 @ 6”o.c.
3” minimum concrete cover on all sides
2000 PLF
36”
6”
3- #4 @ 6”o.c.
48”
6”
3- #4 @ 6”o.c.
60”
6”
3- #4 @ 6”o.c.
72”
8”
3- #5 @ 6”o.c.
84”
10”
3- #5 @ 6”o.c.
96”
12”
3- #5 @ 6”o.c.
1. 3000 psi minimum concrete at approximately 28 days.
2. Grade 40 steel reinforcement minimum.
3. Steel reinforcement at mid-depth of lintel.
[14.7.4.18 NMAC - Rp, 14.7.4.18 NMAC, 11/15/2016]