- (a) The setback and protective well radius requirements specified in We 602.06 through We 602.12, shall not apply to closed loop geothermal wells.
(b) A closed loop geothermal well shall be located no less than:
- (1) Fifty feet from a well used for potable water supply; and
- (2) Twenty five feet from a septic tank or effluent disposal area.
- (c) During advancement of the borehole, the licensed contractor shall follow the observation and record keeping requirements of We 602.20.
(d) The thermal loop used in the borehole shall be:
- (1) Constructed of high-density polyethylene (HDPE) with heat fused couplings; or
- (2) An equivalent loop material and couplings that can be demonstrated to reduce the potential for groundwater contamination by resisting degradation and leakage.
(e) The borehole shall be grouted as follows:
- (1) The entire length of the borehole shall be grouted;
- (2) The borehole shall be grouted in one, continuous effort from the bottom of the borehole using a tremie line;
(3) The grout used in the borehole shall be:
- a. A high-solids bentonite grout;
- b. A cement-sand based grout;
- c. A bentonite-sand based grout; or
- d. Any other grout that has been demonstrated to reduce shrinkage and cracking during multiple heating and cooling cycles; and
(4) The following materials shall not be used as backfill in the borehole when used alone:
- a. Sand;
- b. Gravel;
- c. Pea-stone;
- d. Drilling by-products; or
- e. Other non-cemented or non-grouted, heterogeneous or homogenous mixture of aggregates.
Source. (See Revision Note at chapter heading for We 600) #12083 eff 3-1-17