N.H. Code Admin. R. We 602.16
(a) For a bedrock well that does not comply with the setback requirements of We 602.06 through We 602.12, as applicable, a water well contractor shall:
(1) For a bedrock well with a minimum setback requirement of 75 feet, install casing in accordance with the Table 602-1:
Table 602-1 Minimum Casing Length Where a 75-foot Setback is Required
Horizontal Setback (ft.)
Minimum Length of Casing (ft.)
75 or greater
20
70-74
27
65-69
37
60-64
45
55-59
51
50-54
56
45-49
60
40-44
63
35-39
66
30-34
69
25-29
71
(2) For a bedrock well with a minimum setback requirement of 50 feet, install casing in accordance with the Table 602-2:
Table 602-2 Minimum Casing Length Where a 50-foot Setback is Required
Horizontal Setback (ft.)
Minimum Length of Casing (ft.)
50 or greater
20
45-49
22
40-44
30
35-39
36
30-34
40
25-29
43
Source. (See Revision Note at chapter heading for We 600) #12083 eff 3-1-17