Pursuant to Env-Or 407.06(e), on lots with underground storage tanks the following setbacks shall apply:
- (a) All gasoline underground storage tank systems shall be located at least 500 feet from a public water supply well and at least 250 feet from a non-public water supply well; and
- (b) All regulated substances except gasoline underground storage tank systems shall be located at least 400 feet from a public water supply well and at least 75 feet from a non-public water supply well.
Source. (See Revision Note at chapter heading for We 600) #12083 eff 3-1-17