- (a) A pressure sewer system shall have at least one grinder pump at each building or residence that is connected to the system.
- (b) The minimum capacity requirements for a pressure sewer system and each grinder pump connected to a pressure sewer system shall be determined based on hydraulic modeling of the entire pressure sewer system and the main sewer to which the pressure sewer is proposed to be connected.
- (c) A design report for a pressure sewer system shall be prepared by the engineer and submitted in accordance with Env-Wq 703.01.
- (d) Pressure sewer design shall provide a minimum cleansing velocity of 2 feet per second.
- (e) Pressure sewers shall be constructed with force main materials as specified in Env-Wq 704.08 and tested as specified in Env-Wq 704.09.
(f) Grinder pumps for pressure sewer systems shall be:
- (1) Wet well type;
- (2) Readily removable without manual disconnection of piping;
- (3) Rotating type with a stationary hardened and ground stainless steel shredding ring with stainless steel cutters;
- (4) Capable of reducing all components in typical domestic sewage, including a reasonable number of foreign objects, including but not limited to wood, paper, plastic, glass, and rubber, to a size that will pass through pump passages and a 1.25-inch nominal diameter pipe;
- (5) Positioned so solids are fed into pump from the bottom in an upward flow;
- (6) Capable of processing foreign objects without jamming, stalling, or overloading;
- (7) Accessible for maintenance and replacement; and
(8) Equipped with:
- a. Non-fouling sensing devices for high level alarms;
- b. A visible alarm light;
- c. An audible alarm;
- d. A gravity-operated, integral anti-siphon valve with corrosion-resistant moving parts; and
- e. A suitable receptacle and transfer switch in the electric supply panel for connection to a portable generator.
(g) A grinder pump tank shall be designed to withstand HS-20 loading if installed in a location where traffic loads are anticipated and consist of:
- (1) A manhole meeting the requirements of Env-Wq 704.12 through Env-Wq 704.17;
- (2) A reinforced concrete tank;
- (3) A high density polyethylene tank; or
- (4) A fiberglass-reinforced polyester resin using a filament wound process, layup, and spray technique.
Source. (See Revision Note at chapter heading for Env-Wq 700) #8590, eff 3-25-06; ss by #10693, eff 10-15-14; ss by #14258, eff 7-1-25, EXPIRES: 7-1-35