Design drawings for proposed sewerage shall, in addition to meeting the applicable requirements of Env-Wq 703.01 through Env-Wq 703.03, include the following:
- (a) Contour lines at 2-foot intervals and elevation of existing and proposed project area;
- (b) The locations of all streams and other surface waters within the proposed project area, including their direction of flow and water surface elevations at the time of survey;
- (c) 100-year flood elevations, if available;
- (d) The boundary lines of the municipality, sewer district, or other area to be sewered;
- (e) The location, size, and direction of flow of all existing and proposed sewers;
- (f) Insets and detail sections with the scale shown directly beneath their subtitles;
- (g) Plan and profile views in which the plan view is placed at the top;
(h) Plans clearly showing the location of:
- (1) All existing structures affecting the project;
- (2) Existing and proposed sewer outlets or overflows; and
- (3) All other utilities in the vicinity of the proposed sewerage;
- (i) The locations of existing, proposed, and future sewerage as differentiated by appropriate symbols or designations;
- (j) All topographical symbols and conventions as employed by the USGS;
- (k) The horizontal distance or stationing between manholes, grades in feet per foot, and sewer sizes, types, and class;
- (l) All sewer appurtenances depicted by symbols and referenced by a legend, with detail drawings of all sewer appurtenances accompanying the detail sewerage plans;
(m) Profiles indicating:
- (1) All manholes with manhole identification numbers;
- (2) Existing and proposed water main crossings with elevations;
- (3) Siphons;
- (4) Sewage pumping stations; and
- (5) In the case of stream crossings, the elevations of stream beds, flow lines, and the type of pipe;
- (n) The sizes and gradients of sewers, surface elevations, first floor house elevations, and sewer inverts shown at or between each manhole;
- (o) Finish grade elevations;
- (p) Elevations of manhole inverts shown to the nearest 0.01 foot;
- (q) All elevations referenced to a standard datum that is indicated on the plans; and
- (r) As specified by the engineer, any special precautions or methods of construction necessary to prevent surface water pollution.
Source. (See Revision Note at chapter heading for Env-Wq 700) #8590, eff 3-25-06; ss by #10693, eff 10-15-14; ss by #14258, eff 7-1-25, EXPIRES: 7-1-35