N.H. Code Admin. R. Env-Wq 1504.11
(e) “Q” as used for the calculation of CN in (f), below, means the water quality depth, calculated as WQV divided by A, as shown in the formula below:
Q = WQV / A
(f) “CN” as used for the calculation of S in (g), below, means the unit peak discharge curve number, calculated by dividing 1000 by the value obtained by adding 10 to 5 times P and adding 10 times Q, and then subtracting 10 times the value obtained by adding Q squared to the product of 1.25 times Q times P and raising the sum to the 0.5 power, as shown in the formula below:
CN = 1000 / (10 + 5P + 10Q – 10 x [Q2 + 1.25 x Q x P] 0.5)
(g) “S” as used for the calculation for Ia in (h), below, means the potential maximum retention in inches, calculated by subtracting 10 from the value obtained by dividing 1000 by CN, as shown in the formula below:
S = (1000 / CN) – 10
(h) “Ia” as used in TR-55 exhibits 4-II and 4-III means the initial abstraction, calculated by multiplying 0.2 by S, as shown in the formula below:
Ia = 0.2 x S
(i) To calculate the WQF, the applicant shall multiply qu by WQV, as shown in the formula below:
WQF = qu x WQV