- (a) The owner of a PBF shall change or clean and disinfect all cartridge filters when the pressure differential between the influent and effluent lines of the filter reaches 6 pounds per square inch (psi) or the manufacturer’s recommended pressure differential, if less than 6 psi.
- (b) If no means of measuring the pressure differential is provided, cartridge filters shall be changed or cleaned and disinfected at least once per day.
- (c) Cartridge filters also shall be cleaned and disinfected in a concentrated chlorine solution or replaced in response to a violation of Env-Wq 1108.12.