(a) Holding tanks or closed systems shall not be approved except in the following instances:
- (1) As a replacement for an existing system in failure when no other means of disposal is practical; or
- (2) When the structure proposed to be served by the holding tank will be connected to a municipal sewer within one year of approval of the holding tank application.
(b) Holding tanks shall be:
- (1) Water-tight;
- (2) A minimum of 2,000 gallons in size; and
- (3) Provided with an alarm system to indicate when the tank is full and requires pumping.
- (c) Holding tanks shall meet the minimum separation distance requirements listed in Table 1008-2.
(d) To apply for department approval for a holding tank, the applicant shall complete and submit either electronically at https://www4.des.state.nh.us/OneStopDataProviders/DESLogin.aspx or in paper form the "Application for an Individual Sewage Disposal System", NHDES-W-05-004, February 2026, available at: https://onlineforms.nh.gov/?formtag=NHDES-W-05-004 in addition to the following information:
- (1) The information required by Env-Wq 1003.13 and details of an audible and visual alarm system hardwired back to the building’s electric panel; and
- (2) A copy of the signed contract with a licensed septage hauler that identifies at least one approved disposal site to which the septage will be hauled.
- (d) The owner of the property on which a holding tank has been installed shall:
- (1) Retain all receipts for pumping services for a period of 2 years from the date of the receipt; and
- (2) Submit copies of said receipts to the local health officer on a quarterly basis.
Source. (See Revision Notes #1 and #2 at chapter heading for Env-Wq 1000) #11184, eff 10-1-16; ss by #14486, eff 2-1-26, EXPIRES: 2-1-36