- (a) All effluent conduits for ISDS shall be equivalent to SDR 35 or stronger.
- (b) Supply lines from the distribution box to the effluent conduits shall be unperforated pipe.
- (c) Pipe connections in accordance with manufacturer’s specification shall be used between the effluent conduits.
- (d) The maximum length of an effluent conduit shall be 100 feet.
- (e) Each effluent conduit shall come directly from a separate outlet of the distribution box.
- (f) The effluent conduits shall be sealed into the distribution box with non-shrink mortar or other sealant that can be shown by submission of manufacturer’s literature with the application to be shrink-proof, water proof, and will not deteriorate over time.
- (g) All effluent conduits shall be either interconnected or capped at the far end of the system.
- (h) The effluent conduits and the bottom of the EDA shall be level.
Source. (See Revision Notes #1 and #2 at chapter heading for Env-Wq 1000) #11184, eff 10-1-16; ss by #14486, eff 2-1-26, EXPIRES: 2-1-36