- (a) Each sewage or effluent pump shall have a visual and audible alarm that signals if the pump fails for any reason.
- (b) The alarm shall signal in a centrally-located area that is used daily.
- (c) The pump(s) and the alarm system(s) shall be on separate electronic circuits.