- (a) Manholes shall be provided every 350 feet in long sewer runs and at each change in slope or direction.
- (b) Manholes shall conform to standards set for municipal installations in Env-Wq 700.
- (c) When the run of a gravity sewer designed to carry solids is greater than 100 feet but less than 350 feet with no change in slope or direction such that manholes are not used, a clean-out shall be provided every 100 feet that does not have a septic tank tie-in.
Source. (See Revision Notes #1 and #2 at chapter heading for Env-Wq 1000) #11184, eff 10-1-16; ss by #14486, eff 2-1-26, EXPIRES: 2-1-36