(a) The pressure decay test required by Env-Or 504.07(b) shall be performed:
(b) To pass the pressure decay test, the minimum allowable final pressure after the system has been pressurized to 10 inches water column and held for 5 minutes shall be as specified in Table 500-1, below:
Table 500-1 Minimum Allowable Pressure
Ullage (gallons)
Minimum Allowable Pressure (inches water column)
Ullage (gallons)
Minimum Allowable Pressure (inches water column)
500
3.70
5,000
9.30
600
4.50
6,000
9.38
700
5.20
7,000
9.46
800
5.80
8,000
9.52
900
6.20
9,000
9.56
1,000
6.50
10,000
9.60
1,250
7.05
11,000
9.62
1,500
7.50
12,000
9.64
1,750
7.90
13,000
9.66
2,000
8.20
14,000
9.68
2,250
8.35
15,000
9.70
2,500
8.50
16,000
9.71
2,750
8.60
17,000
9.71
3,000
8.70
18,000
9.72
3,250
8.80
19,000
9.73
3,500
8.90
20,000
9.73
3,750
9.00
21,000
9.74
4,000
9.10
22,000
9.75
4,250
9.15
23,000
9.75
4,500
9.20
24,000
9.76
4,750
9.25
25,000
9.77
Source. (See Revision Note #1 and Revision Note #2 at chapter heading for Env-Or 500) #10229, eff 11-17-12; ss by #13458, eff 10-7-23 (formerly Env-Or 504.10)