(a) As specified in RSA 146-C:8:
- (1) USTs that have been removed and do not meet the requirements of Env-Or 405.01 shall not be reinstalled for the purpose of storing regulated substances; and
- (2) Any tank that has been used for any regulated substance shall not be reused to store food products.
- (b) A tank that has been used to store any regulated substance also shall not be reused to store water.
(c) A tank shall be reinstalled for regulated substance storage only if:
(1) As specified in RSA 146-C:8, it is:
- a. Thoroughly cleaned and inspected, both internally and externally;
- b. As a result of such cleaning and inspecting, found to be structurally sound and free of pinholes, cracks, structural damage, or corrosion; and
- c. Reinstalled in accordance with all applicable requirements of this chapter; and
- (2) Recertified by the tank manufacturer as meeting tank standards for new UST systems.
- (d) A tank shall not be reused as an aboveground storage tank.
Source. (See Revision Note #1 at chapter heading for Env-Or 400) #10393, eff 9-1-18; ss by #12643, eff 10-10-18 (See Revision Note #2 at chapter heading for Env-Or 400)