The following shall apply to UST systems, including but not limited to all associated piping systems, for fueling facilities at which fuel is dispensed over surface waters:
(a) All UST systems shall comply with the following, available as noted in Appendix B:
- (1) NFPA 30, Flammable and Combustible Liquids Code;
- (2) NFPA 30A, Motor Fuel Dispensing Facilities and Repair Garages; and
- (3) NFPA 303, Marinas and Boatyards;
(b) Piping systems where tanks are at an elevation that produces a pressure due to gravity at the dispenser shall:
- (1) Be equipped with an anti-siphon device installed adjacent to and downstream from a manually-operated shutoff valve; and
- (2) Have the anti-siphon device and manual shutoff valve located inside a liquid-tight collection sump at the tank;
- (c) All sumps shall be liquid-tight and have a sump sensor;
(d) Piping systems shall:
- (1) Have continuous secondary containment and be equipped with liquid-tight intermediate sumps with sensors at locations where runs of continuous secondary containment are joined;
- (2) Be equipped with flexible piping with secondary containment between any floating structure and the shore;
(3) Be equipped with a readily-accessible shutoff valve that is:
- a. Located on the shore, as close to the shoreline as possible; and
- b. Installed adjacent to and upstream from the flexible piping required by (2), above; and
- (4) Be protected from physical damage;
- (e) Dispensing nozzles shall be automatic closing type without a device that allows the dispensing nozzle to remain open;
- (f) Piping shall not be in contact with surface water;
(g) Onshore marina dispensers installed on or after the 2018 effective date of this chapter that are designated for filling portable containers only shall have a level reinforced-concrete dispensing pad that:
- (1) Is not less than 5 feet wide by 5 feet long; and
(2) Has positive limiting barriers that:
- a. Have a volume of at least one gallon; and
- b. Are installed as specified in Env-Or 405.07(b)(1) and (2); and
- (h) Onshore marina dispensers that are designated to fuel boated trailers and other land-based equipment shall be constructed in accordance with Env-Or 405.07(b).
Source. (See Revision Note #1 at chapter heading for Env-Or 400) #10393, eff 9-1-18; ss by #12643, eff 10-10-18 (See Revision Note #2 at chapter heading for Env-Or 400)