- (a) Subject to (b), below, secondary containment shall be provided for all underground piping systems that routinely contain regulated substances or their vapors by using double-wall piping.
- (b) Vent piping shall be exempt from (a), above.
(c) All piping and dispenser sumps shall be:
- (1) Liquid-tight to contain liquids;
- (2) Installed to prevent the intrusion of groundwater or surface water runoff; and
- (3) Equipped with liquid-tight penetration fittings for all sump entries.
(d) All piping and dispenser sump sensors shall be installed:
- (1) To respond to small accumulations of liquids within the sumps;
- (2) In the lowest portion of the sump; and
- (3) In accordance with the manufacturer’s requirements for installation.
- (e) Subject to (f), below, all piping that is inside a building and part of the interior piping system shall have secondary containment and leak monitoring that meets the requirements of (a) through (d), above.
- (f) For piping that is inside a building, an engineered pipe trench system may be used as secondary containment in lieu of double-wall piping.
Source. (See Revision Note #1 at chapter heading for Env-Or 400) #10393, eff 9-1-13; ss by #12643, eff 10-10-18 (See Revision Note #2 at chapter heading for Env-Or 400)