(a) The owner of any location at which any oil-filled electrical equipment individually contains more than 660 gallons of oil shall:
- (1) Register with the department in accordance with Env-Or 304.01; and
- (2) Prepare and maintain a spill prevention control and countermeasure plan as specified in Env-Or 306.02.
(b) The owner of any location where any oil-filled electrical equipment that was installed on or after April 25, 1997 individually contains greater than 660 gallons of oil shall have:
- (1) An impermeable barrier in the soil beneath the oil-filled equipment;
- (2) A containment structure, such as a collection sump, that contains and then conveys all liquids to an oil-water separator for collection until treatment can occur;
- (3) Some other engineered solution that will prevent a release of oil from the equipment to surface waters or groundwater of the state; or
- (4) Operational controls sufficient to identify, manage, respond, and prevent a release of oil to the surface waters or groundwater of the state.
Source. (See Revision Note at chapter heading for Env-Or 300) #10487, eff 2-7-14; ss by #14094, eff 10-4-24