(a) Corrosion protection for AST bottoms that were installed on or after April 25, 1997 and are in contact with the soil shall:
- (1) Consist of a sacrificial anode system or an impressed current system designed, fabricated, and installed in accordance with API 651 or NACE SP-0285;
- (2) Be designed and installed with oversight by a corrosion expert;
- (3) Be designed to provide corrosion protection for the expected active life of the AST system or to allow for the periodic rehabilitation of the anode system; and
- (4) Have a test station or other method of monitoring that enables the owner to confirm that the cathodic protection system is operating properly.
- (b) Corrosion protection for piping systems shall be designed and constructed in accordance with NFPA 30, API 1615, API 1632, or NACE SP-0169, as applicable.
- (c) With the exception of insulated tanks and insulated piping addressed as specified in Env-Or 306.07, 306.08, and 306.10, the exterior surfaces of all tanks and exposed piping shall be painted or coated to prevent corrosion or other deterioration.