N.H. Code Admin. R. Env-Dw 714.09
(a) The O/O of a water system that is subject to this part shall comply with the monitoring requirements for water quality parameters specified in 40 CFR §141.87, 7-1-16 edition, as modified by Table 714-1, below, subject to the notes in (b), below:
Table 714-1: Summary of Monitoring Requirements for Water Quality Parameters
Monitoring period; Location
Parameters
Frequency
Initial water quality monitoring:
- Taps
- Entry point(s) to distribution system
- pH
- alkalinity
- conductivity
- water temperature
- calcium A
- orthophosphate B
- silica C
As specified in 40 CFR §141.87, except that the frequency shall be twice in 90 days after the date of action level exceedance
Routine water quality monitoring:
- Taps
- pH
- alkalinity
- calcium A
- orthophosphate B
- silica C
As specified in 40 CFR §141.87, except that the frequency shall be every 3 months for parameters to be reported twice during each monitoring period
- Entry point(s) to distribution system
- pH
- alkalinity D
- inhibitor E
No less frequently than every 2 weeks
Optimal water quality parameters:
- Taps
- pH
- alkalinity
- calcium A
orthophosphate B
- silica C
Every 6 months
- Entry points(s) to distribution system
- pH
- alkalinity D
- inhibitor E
No less frequently than every 2 weeks F
Reduced water quality monitoring:
- Taps
- pH
- alkalinity
- calcium A
- orthophosphate B
- silica C
Every 6 months, annually or every 3 years; reduced number of sites
- Entry point(s) to distribution system
- pH
- alkalinity D
- inhibitor E
No reductions; continues no less frequently than every 2 weeks F
(b) The following notes shall apply to Table 714-1:
Source. #9859, eff 2-8-11; ss by #12181, eff 5-23-17