N.H. Code Admin. R. Env-Dw 703.01
(a) For a community water system, the MCLs and MCLGs for radionuclide contaminants shall be as stated in Table 703-1, below:
Table 703-1: MCLs and MCLGs for Radionuclide Contaminants
Radionuclide Contaminant
MCL
MCLG
Compliance Gross Alpha
15 pCi/L
0 pCi/L
Radium 226 + 228
5 pCi/L
0 pCi/L
Uranium
30 μg/L
0 μg/L
Beta Particle and Photon Radioactivity
4 mrem/year
0 mrem/year
(b) Compliance with radionuclide contaminant MCLs shall be:
Source. #9699, eff 5-1-10; ss by #12665, eff 1-1-19; ss by #12819, eff 6-28-19