N.H. Code Admin. R. Env-A 3511.05
(b) The following equipment, when installed on a HMIWI unit, shall qualify as an air pollution control device:
(c) The owner or operator of each HMIWI unit equipped with an air pollution control device as described in (b), above, shall:
(e) For HMIWI units equipped with an air pollution control device as described in (b)(1), above, the following methods of operation shall constitute violation of the applicable emission limits:
(f) For HMIWI units equipped with an air pollution control device as described in (b)(2), above, the following methods of operation shall constitute violation of the applicable emission limits:
(g) For HMIWI units equipped with an air pollution control device as described in (b)(3), above, the following methods of operation shall constitute violation of the applicable emission limits:
(i) The owner or operator of a HMIWI unit using an air pollution control device other than those devices listed in (b), above, to comply with Env-A 3505 emission limits shall request other site-specific operating parameters to be established during the initial performance test and continuously monitored thereafter by submitting the following information in writing to the department:
(k) The department shall deny a request submitted pursuant to (i), above, if:
(o) Minimum and maximum operating parameters as required in (c), above, shall be as specified in Table 3500-4, as follows:
TABLE 3500-4: OPERATING PARAMETERS TO BE MONITORED AND
MINIMUM MEASUREMENT AND RECORDING FREQUENCIES
Operating parameters to be monitored
Minimum frequency
Control system
Data measurement
Data recording
Dry scrubber followed by fabric filter
Wet scrubber
Dry scrubber followed by fabric filter and wet scrubber
Maximum operating parameters
Maximum charge rate
continuous
once per hour
3
3
3
Maximum fabric filter inlet temperature
continuous
once per minute
3
3
Maximum flue gas temperature
continuous
once per minute
3
3
Minimum operating parameters
Minimum secondary chamber temperature
continuous
once per minute
3
3
3
Minimum dioxin/furan sorbent flow rate
hourly
once per hour
3
3
Minimum HCl sorbent flow rate
hourly
once per hour
3
3
Minimum mercury (Hg) sorbent flow rate
hourly
once per hour
3
3
Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubber
continuous
once per minute
3
3
Minimum scrubber liquor flow rate
continuous
once per minute
3
3
Minimum scrubber liquor pH
continuous
once per minute
3
3
Source. #6938, eff 1-30-99; ss by #8788, eff 1-5-07