N.H. Code Admin. R. Env-A 3504.01
(a) For the purposes of (c), below, to calculate the maximum design waste burning capacity of intermittent or continuous HMIWI units, the following shall apply:
(b) For the purposes of (c), below, to calculate the maximum design waste burning capacity of batch HMIWI units, the following shall apply:
(c) To calculate the maximum design waste burning capacity, the owner or operator of a HMIWI unit subject to the provisions of this chapter shall:
(1) For intermittent and continuous HMIWI, multiply the primary chamber volume by the primary chamber heat release factor and divide the product by the standard waste heating value, as in the formula below:
C = (Pv x 15,000) / 8,500; or
(2) For batch HMIWI, multiply the primary chamber volume by the waste density and divide the product by the typical hours of operation of a batch HMIWI unit, as in the formula below:
C = (Pv x 4.5) / 8
Source. #6938, eff 1-30-99; ss by #8788, eff 1-5-07