- (a) In addition to other requirements set by rule, statute, or other law each registered service technician shall complete and submit “Placed in Service/Inspection Report Form LPG” Rev. 07/14 to the department.
(b) A registered service technician shall furnish the following on “Placed in Service/Inspection Report Form LPG” Rev. 07/14:
- (1) Name of business;
- (2) Full address, including city, state, and zip code;
(3) The following information about the liquid petroleum gas meter:
- a. Make of meter;
- b. Serial number;
- c. Size;
- d. Minimum and maximum rated G.P.M.;
- e. Make of register;
- f. Register model number;
- g. Register serial number;
- h. Whether there is a temperature compensator;
- i. Thermometer well; and
- j. Vapor eliminator;
(4) The following information about the test data:
- a. Type of test;
- b. Flow rate;
- c. Meter temperature 35 gallon;
- d. Meter temperature 70 gallons;
- e. Tank pressure;
- f. Prover pressure;
- g. Prover temperature;
- h. Prover reading to nearest 0.05 gallon and
- i. Meter reading;
(5) If an uncompensated run, the following:
- a. Average meter temperature;
- b. Temperature difference;
- c. Temperature correction factor;
- d. Correction for temperature difference; and
- e. Temperature correction prover reading; and
(6) If either an uncompensated or compensated run, the following:
- a. Correction for prover pressure reading;
- b. Correction for prover temperature;
- c. Corrected prover reading;
- d. Meter reading; and
- e. Net meter error, in cubic inches if desired.
Source. (See Revision Notes #1 and #2 at chapter heading for Agr 1400) #12424, eff 12-1-17