N.D. Admin. Code § 33.1-14-09-20
1. Each steam boiler having a capacity over twenty-five gallons [94.6 liters] must have a bottom blowoff connection fitted with a valve or cock connected to the lowest water space practicable with a minimum size as shown below:
| Minimum Required Safety Valve Capacity in Pounds of Steam/Hour | Steam Boiler Blowoff Piping Valve Size, Inches (Min.) | ||
|---|---|---|---|
| Up | to | 500 | 3/4 |
| 501 | to | 1,250 | 1 |
| 1,251 | to | 2,500 | 1 1/4 |
| 2,501 | to | 6,000 | 1 1/2 |
| 6,001 | and | larger | 2 |
2. Each hot water boiler and each steam boiler having a capacity not exceeding twenty-five gallons [94.6 liters] must have a drain valve connected to the lowest water space practicable. The minimum size of this drain valve is three-quarter inch [1.9 centimeters].
History: Effective July 1, 2020.
General Authority: NDCC 23.1-16-07
Law Implemented: NDCC 23.1-16-07