N.D. Admin. Code § 33.1-14-05-06
The maximum allowable working pressure on a watertube boiler, the tubes of which are secured to a cast iron or malleable iron header, or which have cast iron mud drums, may not exceed one hundred sixty pounds per square inch gauge [1103.17 kilopascals].
History: Effective July 1, 2020
General Authority: NDCC 23.1-16-07
Law Implemented: NDCC 23.1-16-07